Products
Features
Improved the input current wave form distortion which cause by capacitor.
Reduce the rectifier damage times cause by current impact and prevent capacitor over heat
Increase the power factor and recue the DC bus AC pulse.
Suppress grid voltage instant change
Suppress or filter the ripple wave of DC current work together with capacitors, to reduce the negative effect for load.
Working voltage | 220VAC - 1140VAC |
Working frequency | 50/60Hz |
Rated current | 3A to 1600A |
Insulation class | Class F. H |
Operation environment | No need derated suing during -10℃to 45℃, if work in above 45℃, the rated current will be reduce 2% for every 1℃rising. |
| Protection class | IP00-IP22 |
| Overload tolerance capability | 1.5% rated current for 60s |
| Noise | ≤65DB |
| Temperature rise | ≤85K |
| Dielectric strength | Steel wire core 3000VAC/50Hz/5mA/10s no electric arcing puncture |
| Insulation resistor | 1000VDC insulation resistance value ≥100MΩ |
| Working under sea | Level below 2000m |
| Running condition | Temperature-25℃to 45℃, comparative moisture not over 90% |